FM 200 Calculation Software Free Download

FM 200 Calculation required for fire suppression involves several steps and considerations. Here’s a step-by-step guide to help you through the process:

Step-by-Step Calculation

  1. Determine the Volume of the Protected Space:
    • Measure the length, width, and height of the room in meters.
    • Calculate the volume (V) in cubic meters (m³) using the formula: 𝑉=Length×Width×HeightV=Length×Width×Height
  2. Determine the Design Concentration:
    • The design concentration for FM-200 typically ranges from 6.25% to 9% by volume, depending on the fire hazard. This information should be provided in the system’s design specifications or relevant fire protection standards.
    • For this example, let’s use a design concentration (C) of 7%.
  3. Required Mass of FM-200 Calculation:
    • FM-200 has a specific vapor density, and its mass can be calculated using the following formula: Mass of FM-200(𝑀)=𝑉×𝐶100×𝜌Mass of FM-200(M)=V×100C​×ρ
    • Here, 𝜌ρ is the density of FM-200, which is approximately 42 kg/m³ at 20°C.

Example FM 200 Calculation

Let’s assume we have a room with the following dimensions:

  • Length = 10 meters
  • Width = 5 meters
  • Height = 3 meters

1: Calculate the Volume of the Protected Space𝑉=10 m×5 m×3 m=150 m3V=10m×5m×3m=150m3

2: Determine the Design Concentration For this example, we use a design concentration of 7%.

3: Calculate the Required Mass of FM-200𝑀=150 m3×7100×42 kg/m3M=150m3×1007​×42kg/m3𝑀=150 m3×0.07×42 kg/m3M=150m3×0.07×42kg/m3𝑀=441 kgM=441kg

Additional Considerations

  • Safety Factor: It’s often prudent to include a safety factor in your calculations to account for potential leaks or inaccuracies in measurements.
  • System Design and Standards: Ensure that the system design complies with relevant standards such as NFPA 2001, which may have specific requirements and recommendations for FM-200 systems.
  • Discharge Time: The system should be capable of discharging the required amount of FM-200 within 10 seconds to ensure effective fire suppression.
  • Room Integrity: The room should be sufficiently sealed to prevent FM-200 from escaping before it can suppress the fire.
FM 200 Calculation

Final Notes

  • Always consult with a fire protection engineer or professional to ensure that your calculations and system design are accurate and compliant with local regulations and standards.
  • Regular maintenance and testing of the FM-200 system are crucial to ensure it will function correctly in the event of a fire.